Basic unit TITANUS PRO SENS® 2 EB

801522.10

Approval: VdS

As 801521.10, but with front foil for double pipe operation.
  • Pre-configured for connecting a DM-TP-xx detector module
  • Optical status display for alarm and fault indication at the front foil
  • Extendable for integrating up to two DM-TP-xx detector modules to connect a second tube
  • Ports for two suction tubes with outside diameter of 25 mm
  • Port for air return tube

Additional Information:
The previously required isolator and the reset PCB is no longer required to be fitted to this detector and is no longer available to order. The detector is now fitted as standard with the esserbus alarm transponder which incorporates all of the functions for which these devices provided. Isolator not included with delivery, can be optionally ordered under Part No. 788612.

Scope of Delivery:
Pre-configured basic device including esserbus transponder and reset PC board as well as the front foil.
Alarm displayred LED
Alarm current @ 24 V DC240 mA ... 315 mA (w/o reset PCB)
Starting current @ 24V DC (w/o reset PCB)320 mA (w/o reset PCB)
Connecting cable(recommended) pair-wired, screened e.g. I-Y(St)Y n x 2 x 0.8 mm
Connection terminalmax. 1.5 mm²
Operation indicatorgreen LED
Operating voltage14 ... 30 V DC
CE certificate0786-CPD-20791
Colorwhite, similar to RAL 9018
HousingABS plastic
Weight kg approx. 1.35 kg
Cable entry5 x M 20 / 2 x M 25
Beveled tubular plug1 x for ABS tube D=25 mm for return air duct D=25 mm
Contact load relay30 V DC/1 A max. 24 W
Storage temperature-25 °C ... 65 °C
Exhauster life time (12V)43,500 h at 24°C
Air humidity< 95 % (non-condensing)
Quiescent current @ 24 V DCapprox. 295 mA at 9 V fan voltage
Type of protectionIP20
SpecificationEN 54-20
Fault displayyellow LED
Ambient temperature-20 °C ... 60 °C
VdS-NrG 206118
DimensionsW: 200 mm H: 292 mm D: 113 mm