Basic unit TITANUS TOP SENS® 2 EB

801532.10

Approval: VdS

As 801531.10, but pre-configured to receive up to two DM-TT-xx detector modules. Titanus Top Sens 2 EB is directly connectable to esserbus / esserbus PLus. The device is shipped equipped with the front foil for the double pipe operation.
  • Pre-configured for usage with two DM-TT-xx detector modules
  • Optical status display for information alarm, pre-alarm, main alarm and fault indication
  • Integrated bar graph display to optically indicate the current smoke level
  • Ports for two suction tubes with an outside diameter of 25 mm
  • Port for air return tube
  • Possible two-detection-dependency as per VdS directive


Additional Information:
The previously required isolator and the reset PCB is no longer required to be fitted to this detector and is no longer available to order. The detector is now fitted as standard with the esserbus alarm transponder which incorporates all of the functions for which these devices provided. Isolator not included with delivery, can be optionally ordered under Part No. 788612.

Scope of Delivery:
Pre-configured basic device including esserbus transponder and reset PC board as well as the front foil.
Alarm displayred LED
Alarm current @ 24 V DCapprox. 370 mA @ 9 V fan voltage
Starting current @ 24V DC (w/o reset PCB)300 mA (w/o reset PCB)
Connecting cable(recommended) pair-wired, screened e.g. I-Y(St)Y n x 2 x 0.8 mm
Connection terminalmax. 1,5 mm²
Operation indicatorgreen LED
Colorwhite, similar to RAL 9018
HousingABS plastic
Weight kg approx. 1.35 kg
Cable entry5 x M 20 / 2 x M 25
Beveled tubular plug1 x for ABS tube D=25 mm for return air duct D=25 mm
Contact load relay30 V DC/1 A max. 24 W
Exhauster life time (12V)43.500 h at 24°C
Exhauster voltage6,9 V or 9 V
Air humidity< 95 % (non-condensing)
Type of protectionIP 20
Fault displayyellow LED
VdS-NrG206118
DimensionsW: 200 mm H: 292 mm D: 113 mm