Explosion-proof conventional MCP, IP66
        
        
            761697
        
        
            Approval: VdS, PTB 97 ATEX 3197
Explosion-proof encapsulated conventional manual call point for hazardous areas in conformity with EN 54-11 Type B for the manual actuation of a fire alarm and/or a hazard alarm, as a detector for usage in explosion-hazardous areas both inside and outside.
The operating front foil has been designed as a double-sided insert. Complementary to the symbolism conforming to the standards for manual call points in compliance with EN 54-11 (Type B), it has a symbol and multilingual text on the back for the "out-of-order" status of the detector and is always available for possible maintenance work.
The labeling foil of the manual call point also has a double-sided design. In compliance with EN 54-11, it contains the standard symbol of a burning house. On the back, the symbol is supplemented with the word “FIRE” (multilingual). 
        
     
    
        
        
            Additional Information:
Please note, an allen key (size 4) is needed for opening and resetting the manual call point, and is not included in the scope of delivery.  
Scope of Delivery:
1 x Glass pane 704910
1 x Kit of double-sided operating front foil (with "out-of-order" on the back)
1 x Kit of double-sided labeling foil (multilingual) 
        
        
            
    
        
            |  Operating voltage | 
            12 ... 24 V DC | 
        
        
            | Alarm current | 
            approx. 9mA | 
        
        
            | No. of detector/zone | 
            max. 10 detectors per Zone (according to VdS) | 
        
        
            | Application temperature | 
            -55 °C ... 65° C | 
        
        
            | Storage temperature | 
            -55 °C ... 85° C 
             | 
        
        
            | Explosion protection | 
            Ex e d mb IIC T6, T5 | 
        
        
            | Connection terminal | 
            0.6 mm ... 4 mm² | 
        
        
            | Type of protection | 
            IP66 | 
        
        
            | Housing | 
            Glass fiber reinforced polyester resin | 
        
        
            | Air humidity | 
            < 95 % (non condensing) | 
        
        
            | Color | 
            red, similar to RAL 3000 | 
        
        
            | Weight | 
            approx. 1.8 kg | 
        
        
            | Detector specification | 
            DIN 14678 Form K | 
        
        
            | Dimension | 
            W: 136 mm H: 138 mm D: 88mm | 
        
    
  
         
        
            -   704910   Spare glass pane for MCP housings
 -   961650   Cable gland