Aspiration Smoke Detector FAAST LT, 2 channel, 2 detector

801722.10

The ASD FAAST LT uses high sensitivity laser and ultrasonic flow sensors to monitor airflow. This technology allows an early and reliable smoke detection. The detector provides alarm and fault relays with auxiliary events relay as an option. These can be set as latched or non-latched. To accommodate local installation standards or environments, flow and general fault delay can also be set. The system is designed for efficient wiring and installation via cable gland holes and easy access to the wiring area. Also the easy access to filters and sensors makes the routine maintenance easier.
  • Sensitivity 0,07 % obs/m
  • Maximum Single Pipe Length 100 m
  • Maximum Branched Pipe Length 160 m (per channel)
  • Maximum Air Inlet Holes 18
  • Display (depend. on model): alarm level, alarm, pre-alarm, 9 particulate levels, fault status, flow level, test, reset, disable buttons
  • Multiple event logging up to 2240 events
  • Ultrasonic airflow sensing
  • A single device covers up to 2000 m2
  • PipeIQ LT software provides intuitive system layout and configuration
  • User friendly air flow pendulum graph for verification of pipe network functionality
  • Protected electronics from air flow and accidental damage during installation or maintenance
  • Easily replaceable and reusable filter without affecting the rest of the device
Alarm current @ 24 V DCapprox. 570 mA
Operating voltage18.5 ... 31.5 V DC
Weight kg approx. 4.2 kg
Air humidity10 ... 93 % (non-condensing)
Quiescent current @ 24 V DCapprox. 270 mA
Type of protectionIP65
Area to be monitoredmax. 2000 m²
Ambient temperature-10 °C ... 55 °C
DimensionsW: 356 mm H: 403 mm D: 135 mm