FAAST XS

7100XE

The FAAST XS aspirating smoke detector combines advanced particle separation with unique dual source optical smoke detection technology to provide highly sensitive Very Early Warning Fire Detection while providing enhanced immunity to false alarms.
This technology enables FAAST XS to accurately detect incipient fire conditions up to Class A (according to EN54-20), in applications ranging from mission critical to harsh and extreme Environments.
An installed FAAST XS device can administrate up to 170 m pipe length in Standard coverage type applications and can be monitored in several different ways, including: Serial or TCP Modbus, Ethernet over a LAN or a direct connection, or via FAAST XS's onboard USB.
  • Approved for use in Class A, B and C, according to EN54-20
  • Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration
  • Three alarm levels and three sensitivity modes provide application flexibility
  • User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption
  • Ultrasonic flow sensing and chamber airflow Monitoring for precise system health information
  • Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions
  • Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the field-replacement filter
  • TCP and Serial Modbus for easy Integration with building management systems
  • Easy configuration via USP Interface, no external power needed
  • Onboard Ethernet Interface enables remote monitoring, configuration, web Server and E-Mail notifications
  • Multilingual LCD user interface allows for detailed device information
  • Configurable air flow fault thresholds and verification period
Alarm current High - 230 mA
Low - 142 mA
Operating current High - 200 mA
Low - 120 mA
Total Pipe Length 170 m
Total Hole Numbers Class A: 16 holes / Class B: 20 holes / Class C: 20 holes
Operating temperature 0° C ... 38° C ; Factory Tested to 55° C
Sampled Air Temperature -20 °C ... 60 °C
Humidity 10 ... 95 % (non-condensing)
Sensitivity Range 0.00095 % Obs/m to 20.5% Obs/m
Coverage Area max. 2.000 m²
Type of protection IP30
External Supply Voltage 18 - 30 VDC
Dimensions W: 279 mm H: 229 mm D: 159 mm