IR flame detector X 9800

761347

Approval: VdS, FM. ATEX

The pressure-proof, fully enclosed infrared flame detector particularly distinguishes itself through reliable operation in difficult conditions. An integrated LED and three relays provide information regarding the state of operation, failure, and alarm. Contamination resistance and heated optics to prevent condensation and formation of ice also allow for external operation. Typical areas of application are turbines, petrochemistry and the automotive industry.

Monitoring on the loop and resetting take place via the esserbus transponder 808623. Monitoring on a conventional line requires a reset module. This device requires a separate voltage supply of 24 V DC.
  • Visual range: 90°
  • Maintenance with magnets, no test lamp required
  • Status display directly at the detector via 3-color LED for operation, fault and alarm
  • Monitoring and resetting via esserbus transponder 808623 in loop operation


Additional Information:

Please note: for mounting of the holder, a 14 mm allen key is necessary and is not included in delivery.
If you intend to use the internal heater the current consumption raises to 567 mA @ 30 V DC.

Scope of Delivery:

Mounting bracket, 1 x metal EX cable gland
Displaymax. 25 m
EC-type examination certificateDEMKO 02 ATEX 132195
Operating voltage24 V DC
CE certificate0786-CPD-20779
Ex-categoryII 2 GD
Explosion protectionEEx d IIC T5-T6, T86°C
HousingDie cast aluminum
Weight kg approx. 2.7 kg (+ 6.0 kg fixture)
Storage temperature-55 °C ... 85 °C
Detector specificationEN 54-10, Class 1
Air humidity< 95 % (non-condensing)
Type of protectionIP66
Angle of visionmax. 90°
Current consumption @ 24 V DCapprox. 87.5 mA
Height to be monitoredmax. 20 m
Ambient temperature-40 °C ... 75 °C
VdS classF
VdS-NrG 203084
Dimensionsø: 122 mm H: 246 mm