UV/IR flame detector X 5200

761349

Approval: VdS, FM, ATEX

The pressure-proof, fully enclosed combination ultraviolet/infrared flame detector, enables UV and IR sensors to monitor the same detection zone with a visual angle of 90?. Triggering occurs only by activation of the IR and UV sensors. A LED provides information regarding the state of operation, failure and alarm. Three relays (fire, failure and additional alarm) are integrated for connection to a fire detection system. Contamination resistance and heated optics to prevent condensation and formation of ice also allow for external operation.
Typical areas of application are turbines, munitions depots, natural gas depots and aircraft hangers.

Monitoring on the loop and resetting take place via the esserbus transponder 808623. Monitoring on a conventional line requires a reset module. This device requires a separate voltage supply of 24 V DC.
  • Visual range: 90°
  • Maintenance with magnets, no test lamp required
  • Status display directly at the detector via 3-color LED for operation, fault and alarm
  • Actuation and resetting via esserbus transponder 808613.10 in loop operation

Additional Information:
Please note: for mounting of the holder, a 14 mm allen key is necessary and is not included in delivery.
If you intend to use the internal heater the current consumption raises to 583 mA @ 30 V DC.

Scope of Delivery:
Mounting bracket, 1 x metal EX cable gland
Displaymax. 25 m
EC-type examination certificateDEMKO 02 ATEX 132195
Operating voltage24 V DC
Ex-categoryII 2 GD
Explosion protectionEEx d IIC T5-T6, T86°C
HousingDie cast aluminum
Weight kg approx. 2.7 kg (+ 6.0 kg fixture)
Storage temperature-55 °C ... 85 °C
Detector specificationEN 54-10, Class 1
Air humidity< 95 % (non-condensing)
Type of protectionIP66
Angle of visionmax. 90°
Current consumption @ 24 V DCapprox. 117 mA
Height to be monitoredmax. 20 m
Ambient temperature-40 °C ... 75 °C
VdS classF
VdS-NrG 203085
Dimensionsø: 122 mm H: 246 mm