Fireray Eexd, line smoke detector for EX areas

761318

Approval: VsS, LPCB, ATEX

Explosion-proof infrared line smoke detector.

Consisting of transmitter, receiver, and remote evaluation unit for light and dark smoke.

Integrated on the loop and the resetting function is carried out via the esserbus transponder 808623.
Integration on a conventional line requires use of a reset module. The detector requires a separate voltage supply of 24 V DC.
  • Low current consumption
  • Automatic self check drift compensation
  • 3 x selectable sensitivity/threshold levels
  • Remote/low level control equipment (safe area)
Alarm current @ 24 V DC 16,5 mA mA
Approval type VdS, LPCB, ATEX
Operating voltage 11.5 ... 28 V DC
CE certificate 0786-CPD-20176
Explosion protection II 2 GD EEx d IIB T6
Weight kg approx. 4 kg (transmitter/receiver); approx. 1.1 kg (evaluating unit)
Range 10 ... 100 m
Quiescent current @ 24 V DC approx. 8 mA
Type of protection IP 67 (transmitter/receiver)
Ambient temperature -20 °C ... 55 °C
Dimensions W: 210 mm H: 260 mm D: 88 mm (evaluation unit)