Basic unit TITANUS PRO SENS® 2 EB with silent fan

801522.10.SL

Approval: VdS


Same as 801522.10, but with premounted SL fan for operation in noise-sensitive areas. With the SL-fan, the operating noise of the device drops to 23 dB (A) depending on the environmental conditions.
  • Pre-configured for connecting a DM-TP-xx detector module
  • Optical status display for alarm and fault indication at the front foil
  • Extendable for integrating up to two DM-TP-xx detector modules to connect a second tube
  • Ports for two suction tubes with outside diameter of 25 mm
  • Port for air return tube

Scope of Delivery:
Pre-configured basic device including esserbus transponder and reset PC board as well as the front foil.
Alarm displayred LED
Alarm current @ 24 V DC240 mA ... 315 mA (w/o reset PCB)
Starting current @ 24V DC (w/o reset PCB)320 mA (w/o reset PCB)
Connecting cable(recommended) pair-wired, screened e.g. I-Y(St)Y n x 2 x 0.8 mm
Connection terminalmax. 1.5 mm²
Operation indicatorgreen LED
Operating voltage14 ... 30 V DC
CE certificate0786-CPD-20791
Colorwhite, similar to RAL 9018
HousingABS plastic
Weight kg approx. 1.35 kg
Cable entry5 x M 20 / 2 x M 25
Beveled tubular plug1 x for ABS tube D=25 mm for return air duct D=25 mm
Contact load relay30 V DC/1 A max. 24 W
Storage temperature-25 °C ... 65 °C
Exhauster life time (12V)43,500 h at 24°C
Air humidity< 95 % (non-condensing)
Quiescent current @ 24 V DCapprox. 295 mA at 9 V fan voltage
Type of protectionIP20
SpecificationEN 54-20
Fault displayyellow LED
Ambient temperature-20 °C ... 60 °C
VdS classF
VdS-NrG 206118
DimensionsW: 200 mm H: 292 mm D: 113 mm