Detector module 0.015 %/ m DM-TT-01L

801535.10

As 801534.10 but, with a higher response sensitivity of 0.015 % light opacity/m.
  • Response sensitivity adjustable at the module
  • Fast commissioning through automatic initializing process
  • Status display for status and fault diagnosis
  • Installation into Titanus Pro Sens EB without tools
  • Air flow monitoring for detecting pipe burst and tube blockage
HousingABS plastic
Weight gapprox. 100 g
Ambient temperature-20 °C ... 60 °C